  • 产品名称: CM5 / CM5Z / CM5Z / CM5ZL Molded Case Circuit Breaker CM5G Disconnector

Overview

CM5, CM5Z, CM5Z, CM5ZL plastic shell circuit breaker (hereinafter referred to as circuit breaker) is a double breakpoint structure technology research and development with the international advanced level of the new generation of circuit breakers, divided into four series:

——Thermocouple adjustable CM5 series circuit breakers are 63A, 125A, 160A, 250A, 400A, 630A six shell, current from 1.5 A ~ 630A.
——Intelligent CM5Z series circuit breakers are 125A, 160A, 250A, 400A, 630A, 1600A six shell, current from 12.5A ~ 1600A.
——with residual current protection thermo-magnetically adjustable CM5L series circuit breakers are 125A, 250A, 400A, 630A four shell, the current from 1.5 A ~ 630A, the remaining current from 30mA ~ 3A.
——with residual current protection Intelligent CM5ZL series circuit breakers have 125A, 250A, 400A, 630A four shell, current from 12.5A ~ 630A, the remaining current from 30mA ~ 3A.

CM5Z, CM5ZL intelligent circuit breaker optional variety of intelligent release, including the E-type, Z-and iP-type. IP type with a comprehensive power monitoring function, can provide specifications for the 250,400,630 shell.
CM5G series of isolation switch for the CM5 derived products, with standard CM5 Molded Case circuit breaker size, convenient set of factory standardized design.
The circuit breaker is divided into L type (standard type), M type (higher breaking type), type H type (high breaking type), S type (ultra high breaking type) four levels by rated short circuit breaking capacity (Icu) The
Circuit breaker voltage level, the short-circuit breaking capacity level can be inverted line connection.
The circuit breaker can be mounted on a vertical mounting plate or mounted on a horizontal mounting plate.
The circuit breaker has the isolation function, the corresponding symbol is:.
CM5L, CM5ZL circuit breaker can be built-in residual current alarm does not trip module, to avoid significant losses caused by power failure to meet GB13955 Article 4.6 requirements.
The product meets the following criteria:
IEC 60947-1 and GB 14048.1 General requirements for low - voltage switchgear and control equipment
IEC 60947-2 and GB 14048.2 Low voltage switchgear and controlgear circuit breakers
IEC60947-3 and GB14048.3 Low-voltage switchgear and controlgear Switches, isolators, disconnectors and fuse combinations
IEC60947-4-1 and GB 14048.4 Low-voltage switchgear and control equipment Electromechanical contactors and motor starters (including motor protector)

Regular Service Conditions

The ambient air temperature is -5 ℃ ~ +40 ℃;
Installation of the altitude of not more than 2000m;
The relative humidity of the air at the installation site is no more than 50% at a maximum temperature of + 40 ° C and a higher relative humidity at a lower temperature, for example 90% at 20 ° C. Special measures should be taken for occasional condensation due to temperature changes;
Pollution level of 3;
The circuit breaker through GB / T2 423.10 test requirements can withstand the frequency of 2Hz ~ 13. 2Hz, displacement of ± 1mm ​​and frequency of 13.2Hz ~ 100Hz, the acceleration of ± 0.7g mechanical vibration;
Circuit breaker main circuit installation category Ⅲ, the rest of the auxiliary circuit, the control circuit installation category Ⅱ;
Circuit breaker for electromagnetic environment A;
Wet type (TH type) circuit breaker through GB / T2423.4, GB / T2423.18 test requirements, can withstand moisture, salt spray, oil mist, mold the impact;
The circuit breaker shall be installed in an explosion-free and non-conductive dust, where it is not sufficient to corrode the metal and destroy the insulation;
The circuit breaker should be installed where there is no rain or snow;
Operational conditions:
The circuit breaker can pass the GB / T 2423.1 and GB / T2423.2 test requirements, the ambient air temperature can be as low as -25 ℃, up to +70 ℃ (more than +40 ℃ derating use, see the sample of technical information);
Altitude to 2500m characteristics are not affected (more than 2500m derating use, see the sample in the technical information);
Storage conditions: the ambient air temperature is -40 ℃ ~ +70 ℃.