  • 产品名称: CW2 Series Intelligent Universal Circuit Breaker

Overview

The circuit breaker is suitable for AC 50Hz/60Hz distribution networks with the rated working voltage of 400V, 690V and 1,000V and the rated current of 6,300A or below, and is used for distributing electric energy and protecting circuits and equipment from overload, short circuit, under-voltage, ground faults and other hazards. Due to the adoption of a multifunctional intelligent controller with accurate selective protection, it is particularly suitable for distribution networks needing power supply reliability to prevent unnecessary power failure. Circuit breakers with the rated current of 1,000A or below can be used as overload, short circuit, under-voltage and ground fault protection for motors in AC 50Hz and 400V networks, and can also be used for unfrequent starting of motors under normal conditions.
 

√High performance, small volume, perfect and reliable protection, isolating function;
√Higher circuit breaking and short circuit withstand capacity, service short-circuit breaking capacity Ics=ultimate short-circuit breaking capacity Icu;
√The circuit breaker can be equipped with different intelligent controllers to provide diversified solutions;
√Safety use, superior performance: the panel has intuitive switch-on ready indications; the drawer type has three position indications, “Connect”, “Test” and “Separate”, as well as locking devices (patented technologies);
√The main loop wiring terminal is convenient to connect, which can realize horizontal connection, vertical connection and mixed connection;
√A zone selective interlocking function can be selected to ensure complete selectivity of protection of all levels;
√It can realize intelligent network monitoring, and can be applied to Modbus, Profibus, Devicenet, CAN and TCP communication protocols, facilitating in integrated management of users;
√It can be equipped with FDM3 SMS notification module, to realize remote warning and monitoring;
√It accords with IEC60947-2 and GB14048.2 standards;
√The circuit breaker has obtained the “CCC” mark.

 

Regular Service Conditions

 The ambient air temperature of -5℃~+40℃, and the average value in 24 hours is not more than +35℃;
The elevation of installation sites cannot be more than 2,000m;
The relative air humidity cannot be more than 50% at the highest temperature of +40℃; relatively high humidity such as 90% at 20℃ is available at relatively low temperature; please take special measures to remove condensation occasionally generated by temperature variation;
The pollution grade is III;
The installation category of the main circuit of the circuit breaker, a UVT coil and the primary coil of a power transformer is IV, while the installation category of the other auxiliary circuits and control circuits is III;
The circuit breaker is suitable for electromagnetic environment A;
Damp and tropical type (TH type) circuit breakers can resist to the influences of humid air, salt mist, oil mist and mildew;
The vertical gradient of the circuit breaker during installation is not more than 5°;
The circuit breaker should be installed in places without explosion hazards, conducting dust, metal corrosion and insulation damages;
The circuit breaker should be installed in small cabinet chambers, and be equipped with door frames, with the protection level up to IP40.